T15 -33kV 9P

Specifications

Applicable up to 6/12 MVA
Rated voltage 33 kV
Rated through-current 100 A / 200A
Insulating Medium AIR
Direction of power flow Uni-Directional( Suitable For BI Directional Also )
Tapping arrangement Selector diverter
Arcing contact Vaccum Interupter
Maximum No of tab position 9
Rated step voltage 900 V
Switching Capacity 180 kVA
Rated Insulation level Highest voltage for equipment kV Rated separate source AC withstand voltage kV(r.m.s) Rated lightning impulse withstand voltage kV(peak)
(a)Tapchanger to ground 36kV 70kV 170kV
(b)Between phases 70kV 170kV
(c)Over tapping range 15kV 40KVp
(d)Between contacts 5kV 15KVp
(e)Between contacts of pre selector NA NA
Oil quantity NA
Weight of tap changer with oil 560 KG

T15 -33kV 9P

Vacuum Circuit breaker

Weldable Bushings

RCS 12

Capacitor Switch

Load Break Switch

RCS 36