T14 33kV 17P C/F

Specifications

Rated Voltage 33 KV  
Rated Current 200 A  
Direction of Power Flow Bi-Directional  
Tapping Arrangement Coarse Fine  
Maximum Number of Tap Positions 17  
Maximum Step Voltage 900V  
Swiching Capacity 90 KVA  
Insulation Level Applied Voltage (KV) Fullwave Lightnining Impulse (KV)
A) Tap Changer to Earth 70 170
b) Between phases 70 170
c) Between First and Last Contacts 25 70
d) Between any two adjacent Contacts 25 70
e) Between contacts of Change – Over Selector 25 70
Oil Quantity 120 Liters  
Weight of OLTC with Oil 320 Kg