Specifications

Rated voltage 66 KV
Rated through-current 300 A
Direction of power flow Bi-Directional
Tapping arrangement Linear
Maximum Number of Tap Positions 17
Max. Rated Step Voltage 1000 V
Switching Capacity 270 KVA
Rated Insulation level Applied voltage (KV) Full wave lightning impulse test (KV)
(a)Tap-changer to Earth 140 385
(b)Between phases 140 350
(c)Between First and Last Contact 40 100
(d)Between any two adjacent contacts 20 50
(e)Between contacts of Change-Over selector NA NA
Oil quantity 535 liters
Weight of tap changer with oil 1000 Kgs.