T11-66 KV -17 Position

Specifications

Rated Voltage 66 KV
Rated Current 300 A
Direction of Power Flow Bi-Directional
Tapping Arrangement Linear
Maximum Number of Tap Positions 17
Maximum Step Voltage 1000V
Switching Capacity 270 KVA
Insulation Level Applied Voltage (KV) Fullwave Lightning Impulse (KV)
A) Tap Changer to Earth 140 350
b) Between phases 140 350
c) Between First and Last Contacts 40 100
d) Between any two adjacent Contacts 25 50
e) Between contacts of Change – Over Selector NA NA
Oil Quantity 580 Liters
Weight of OLTC with Oil 1000 Kg