Specifications

Type reference KS 12
Applicable standard IEC 62271-100/IS 13118
Rated voltage 11kV
1 min A.C withstand test level 35kV
Impulse withstand 75kVp
Current ratings 630A
Operating Sequence O-0.3sec-CO-3min-CO
Rated Short Circuit Withstand Current 16kA for 3 Sec
Rated Peak Withstand Current 40kA Peak
Rated Short Circuit Breaking Current 16kA R.M.S
Rated Short Circuit Making Current 40kA Peak
Degree of Protection IP55